Aim to reduce air change rates, thereby cutting energy demand
Sector: Pharmaceutical
Client: Sterile pharmaceutical manufacturer
Location: Australia
HVAC designed to provide Grade A room conditions at high energy cost is now only required to provide Grade C room conditions for a BFS filling line.
Phase 1 brief was a trial for four out of eight rooms to reduce air change rate and therefore energy demand while maintaining the required airflow patterns for product protection. Phase 2 brief was to deliver air change rate reductions on all 8 rooms based on Phase 1 lessons learnt.
Energy savings delivered per year: 455,000 kWh
Energy cost savings per year: A$63,700
Emissions reduction per year: 387 tonnes CO2
EECO2 delivered the HVAC design review, re-commissioned the HVAC system & carried out the validation testing to protocol. EECO2 then delivered the additional savings on the remaining rooms based on findings and lessons learned during phase.